AS/NZS 5000/PVC Insulated, PVC Sheathed 4 core+E Armored Cables 0.6/1kV
APPLICATIONThis series of PVC insulated PVC sheathed steel wire armoured power cables (hereinafter referred to as "this cable") is specially designed for low-voltage power transmission and is widely used for power supply of main power lines,…
72 PVC Insulated, PVC Sheathed 4 core+E ArmoredCables 0.6_1kV.pdf Contact us

APPLICATION

This series of PVC insulated PVC sheathed steel wire armoured power cables (hereinafter referred to as "this cable") is specially designed for low-voltage power transmission and is widely used for power supply of main power lines, secondary distribution lines, and branch circuits in scenarios such as construction projects, industrial plants, and municipal facilities. It supports multiple laying methods: open laying (exposed installation without mechanical protection), conduit laying (protected by metal/plastic conduits), direct burial laying (directly buried in underground soil), and underground pipeline laying (via prefabricated underground utility corridors). It is especially suitable for indoor and outdoor environments with non-violent mechanical impacts and no frequent external collisions (such as office buildings, cable shafts in factories, and underground non-heavy-load areas, etc.).

STANDARD

  • AS/NZS 5000.1

  • AS/NZS 3008

  • AS/NZS 1125

CONSTRUCTION

ConductorPlain annealed copper.
InsulationPolyvinylchloride compound PVC V-90
Insulation colour:4C + E - Red, White, Blue, black, Green/yellow
Bedding:Polyvinylchloride compound PVC 5V-90
Bedding colour:Black
Armour:Galvanised Steel Wire
Sheath:Polyvinylchloride compound PVC 5V-90
Sheath colour:Orange, other colors are available upon request

TECHNICAL CHARACTERISTICS

ConductorCurrent RatingsElectrical Characteristics
Nominal Area
mm^2
Unenclosed In Air
A
Buried Direct
A
Buried In Ducts
A
Maximum DC Resistance @20°C
Ohm/km
Maximum AC Resistance @75°C
Ohm/km
Reactance
Ohm/km
Single Phase Voltage Drop @75°C
mV/Am
1.515241913.616.50.11128.6
2.52234267.419.010.10215.6
42944344.615.610.1029.71
63755433.083.750.09676.49
105174571.832.230.09063.86
166896741.151.400.08612.43
2591125960.7270.8840.08531.54
351101501150.5240.6380.08261.11
501351801400.3870.4710.07970.829
701702201750.2680.3270.07700.583
952152652100.1930.2360.07660.431
1202453002400.1530.1880.07430.351
1502803352700.1240.1530.07450.296
1853253803100.09910.1230.07440.251
2403854403700.07540.09550.07350.210

CABLE PARAMETER

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
Nom. earth conductor area
mm^2
Nom. earth conductor insulation thickness
mm
Nom. diameter over bedding
mm
Armour diameter mmNom. overall diameter
mm
Approx. mass
kg/km
1.57/0.500.81.50.610.70.916.3545
2.57/0.670.82.50.712.00.917.6635
47/0.851.02.50.713.91.2520.2900
67/1.041.02.50.715.91.2522.21050
107/1.351.04.01.017.51.624.51490
167/1.701.06.01.021.21.628.21810
257/2.141.26.01.024.41.632.22530
357/2.651.2101.026.11.633.32990
5019/1.891.4161.030.42.038.84140
7019/2.241.4251.235.12.043.75470
9519/2.651.6251.239.62.549.67250
12019/2.941.6351.243.92.554.19090
15019/3.281.8501.448.52.559.19900
18537/2.652.0701.454.32.565.412110
24037/2.942.2951.661.63.1574.716320