whatsapp
backtop
AS/NZS 5000/PVC Insulated, Round Cables, 450/750V
APPLICATIONPVC-insulated cables, specially designed for low-voltage control and power transmission, combine the signal stability of control cables with the transmission reliability of power cables, making them an ideal choice for commercial, industria…
43 PVC Insulated, Round Cables, 450_750V.pdf Contact us

APPLICATION

PVC-insulated cables, specially designed for low-voltage control and power transmission, combine the signal stability of control cables with the transmission reliability of power cables, making them an ideal choice for commercial, industrial, mining, and power systems.”PVC-insulated cables, specially designed for low-voltage control and power transmission, combine the signal stability of control cables with the transmission reliability of power cables, making them an ideal choice for commercial, industrial, mining, and power systems.

STANDARD

  • AS/NZS 5000.2

  •  

  • AS 1125

  • AS 3808

CONSTRUCTION

ConductorPlain annealed copper.
Maximum operating temperature: 90°C
InsulationPVC V90.
Insulation colour:2C: Red, Black
3C: Red, White & Blue
4C: Red, White, Blue, & Black
7-37C: White (Numbered)
Sheath:Polyvinylchloride compound PVC 5V90
Sheath colour:Black, other colors are available upon request

TECHNICAL CHARACTERISTICS

ConductorCurrent RatingsElectrical Characteristics
Nominal Area
mm^2
Unenclosed In Air
A
Buried direct
A
Buried In Ducts
A
Maximum DC Resistance @20°C
Ohm/km
Maximum AC Resistance @90°C
Ohm/km
Reactance
Ohm/km
Single Phase Voltage Drop @90°C
mV/Am
2 cores
1.521312413.616.50.11133.0
2.53044347.419.010.10218.0
3 cores
1.517262113.616.50.11128.6
2.52537297.419.010.10215.6
43348374.615.610.1029.71
64261473.083.750.0976.49
4 cores
1.517262113.616.50.11128.6
2.52537297.419.010.10215.6
43348374.615.610.1029.71
64261473.083.750.0976.49
7-37 cores
1.014211718.125.80.11951.6
1.517262113.616.50.11133.0
2.52537297.419.010.10218.0

CABLE PARAMETER

2 cores

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
Nom. sheath thickness
mm
Nom. overall diameter
mm
Approx. mass kg/km
1.57/0.500.60.98.095
2.57/0.670.719.6140

3 cores

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
Nom. sheath thickness
mm
Nom. overall diameter
mm
Approx. mass kg/km
1.57/0.500.60.98.5120
2.57/0.670.7110.1170
47/0.850.81.111.7240
67/1.041.01.113.2300

4 cores

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
Nom. sheath thickness
mm
Nom. overall diameter
mm
Approx. mass kg/km
1.57/0.500.60.99.2130
2.57/0.670.7111.4210
47/0.850.81.112.4280
67/1.041.01.113.8330

7 cores

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
Nom. sheath thickness
mm
Nom. overall diameter
mm
Approx. mass kg/km
1.01/1.130.60.910.0150
1.57/0.500.60.911.4195
2.57/0.670.7113.3300

12 cores

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
Nom. sheath thickness
mm
Nom. overall diameter
mm
Approx. mass kg/km
1.01/1.130.60.912.9240
1.57/0.500.60.915.0320
2.57/0.670.7117.5490

19 cores

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
Nom. sheath thickness
mm
Nom. overall diameter
mm
Approx. mass kg/km
1.01/1.130.60.914.9350
1.57/0.500.60.916.8450
2.57/0.670.7121.0760

27 cores

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
Nom. sheath thickness
mm
Nom. overall diameter
mm
Approx. mass kg/km
1.01/1.130.60.917.9480
1.57/0.500.60.921.1670
2.57/0.670.7124.81030

37 cores

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
Nom. sheath thickness
mm
Nom. overall diameter
mm
Approx. mass kg/km
1.01/1.130.60.921.2690
1.57/0.500.60.922.7840
2.57/0.670.7127.91380