whatsapp
backtop
Profibus L2 Indoor
APPLICATION AND DESCRIPTIONThis system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the information exchange between different automation systems as well as for communication wi…
PROFIBUS L2 INDOOR ..pdf Contact us

APPLICATION AND DESCRIPTION

This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the information exchange between different automation systems as well as for communication with the connected decentralized field units, serial fieldbus systems are used. The types mentioned here are suitable for indoor laying and are equipped with a special PVC jacket.

CONSTRUCTION

Type/Area of Application : Fixed Installation, Indoor

Cable Construction : 1x2x0.64 mm

Inner Conductor Diameter : Copper, bare (AWG 22/1)

Conductor Insulation : Foam-skin-PE

Conductor Colors : Red, green

Stranding Element : 2 conductors + 2 fillers stranded together

Shielding : Polyester foil, aluminum-lined

Total Shielding : Cu braid, tinned

Outer Jacket Material : PVC

Outer Diameter : 7.8 mm ± 0.4 mm

ELECTRICAL DATA

Characteristic Impedance@3-20MHz150 Ω ± 10 Ω
Conductor Resistance55.0 Ohm/km max.
Insulation Resistance1.00 GOhm x km min.
Mutual Capacitance@1 KHz30.0 nF/km nom.
Working VoltageMax: 250 V
Test Voltage1.5 KV
Attenuation9.6kHz<2.5dB/km

38.4kHz<4dB/km

4MHz<22dB/km

16MHz<42dB/km

TECHNICAL DATA

Weightapproximately 69.0 kg/km
Min. Bending Radius (Laying)15 x OD mm
Operating Temp.Range, min.-40 °C
Operating Temp.Range, max.+70 °C