H05G-U / H07G-U/R cables, strictly complying with the French NF C 32-102-7 standard, are the preferred solution for internal precision wiring in electrical control cabinets and distribution boxes, and are also suitable for internal and surface connection lines of lighting fixtures. With excellent high-temperature resistance, they are particularly suitable for heating equipment with a rated AC voltage of 1000V or DC voltage of 750V, ensuring stable transmission in high-temperature environments.
NF C 32-102-7
Solid bare copper / strands
Strands to VDE-0295 Class-1/2, IEC 60228 Class-1/2
Rubber compound type EI3 (EVA) to DIN VDE 0282 part 7 insulation
Cores to VDE-0293 colors
Working voltage : 300/500v (H05G-U), 450/750v (H07G-U/R)
Test voltage : 2000volts (H05G-U), 2500 volts (H07G-U/R)
Flexing bending radius : 7 x Ø
Static bending radius : 7 x Ø
Flexing temperature : -25ºC to +110ºC
Static temperature : -40ºC to +110ºC
Short circuit Temperature : +160ºC
Flame retardant : NF C 32-070
Insulation resistance : 10 MΩ x km
AWG | No. of Cores × Nominal Cross Sectional Area | Nominal Thickness of Insulation | Nominal Overall Diameter | Nominal Copper Weight | Nominal Weight |
---|---|---|---|---|---|
# × mm² | mm | mm | kg/km | kg/km | |
H05G-U | |||||
20 | 1 x 0.5 | 0.6 | 2.1 | 4.8 | 9 |
18 | 1 x 0.75 | 0.6 | 2.3 | 7.2 | 12 |
17 | 1 x 1 | 0.6 | 2.5 | 9.6 | 15 |
H07G-U | |||||
16 | 1 x 1.5 | 0.8 | 3.1 | 14.4 | 21 |
14 | 1 x 2.5 | 0.9 | 3.6 | 24 | 32 |
12 | 1 x 4 | 1.0 | 4.3 | 38 | 49 |
H07G-R | |||||
10(7/18) | 1 x 6 | 1.0 | 5.2 | 58 | 70 |
8(7/16) | 1 x 10 | 1.2 | 6.5 | 96 | 116 |
6(7/14) | 1 x 16 | 1.2 | 7.5 | 154 | 173 |
4(7/12) | 1 x 25 | 1.4 | 9.2 | 240 | 268 |
2(7/10) | 1 x 35 | 1.4 | 10.3 | 336 | 360 |
1(19/13) | 1 x 50 | 1.6 | 12.0 | 480 | 487 |