Type G cable is the ideal choice for mobile mining equipment, providing safe and reliable power to continuous mining machines, cutters, conveyors, drills, and pumps. It is suitable for various mining applications.
ICEA S-75-381/NEMA WC 58
ASTM B 172
ASTM B 33
CAN/CSA C22.2 No. 96
Conductors | Stranded annealed tinned copper conductor. |
---|---|
Insulation | Ethylene Propylene Rubber (EPR). |
Grounding Conductor | Tinned copper conductor with an optional green outer covering. |
Jacket | Reinforced heavy-duty/extra-heavy-duty Chlorinated Polyethylene (CPE), black. (Cables having a nominal outside diameter of more than 2.0 inches require extra-heavy-duty jackets.) |
Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.
Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.
Minimum Bending Radius | 6×OD |
---|---|
Maximum Conductor Operating Temperature | +90℃ |
Construction | No. of Strands | Grounding Conductor Size | Nominal Insulation Thickness | Nominal Jacket Thickness | Nominal Overall Diameter Height×Width | Nominal Weight | Ampacity | ||||
---|---|---|---|---|---|---|---|---|---|---|---|
No. of cores × AWG/kcmil | - | AWG/kcmil | inch | mm | inch | mm | inch | mm | lbs/kft | kg/km | A |
3×8 | 133 | 10 | 0.06 | 1.5 | 0.125 | 3.2 | 0.91 | 23.1 | 590 | 878 | 59 |
3×6 | 168 | 10 | 0.06 | 1.5 | 0.140 | 3.6 | 1.01 | 25.7 | 760 | 1131 | 79 |
3×4 | 259 | 8 | 0.06 | 1.5 | 0.155 | 3.9 | 1.17 | 29.7 | 1070 | 1592 | 104 |
3×3 | 329 | 8 | 0.06 | 1.5 | 0.155 | 3.9 | 1.24 | 31.5 | 1280 | 1904 | 120 |
3×2 | 259 | 8 | 0.06 | 1.5 | 0.155 | 3.9 | 1.34 | 34.0 | 1530 | 2276 | 138 |
3×1 | 329 | 7 | 0.08 | 2.0 | 0.170 | 4.3 | 1.51 | 38.4 | 1890 | 2812 | 161 |
3×1/0 | 259 | 6 | 0.08 | 2.0 | 0.170 | 4.3 | 1.65 | 41.9 | 2320 | 3452 | 186 |
3×2/0 | 329 | 5 | 0.08 | 2.0 | 0.190 | 4.8 | 1.75 | 44.5 | 2700 | 4017 | 215 |
3×3/0 | 413 | 4 | 0.08 | 2.0 | 0.190 | 4.8 | 1.89 | 48.0 | 3270 | 4865 | 249 |
3×4/0 | 532 | 3 | 0.08 | 2.0 | 0.205 | 5.2 | 2.04 | 51.8 | 3970 | 5907 | 287 |
3×250 | 608 | 2 | 0.095 | 2.4 | 0.220 | 5.6 | 2.39 | 60.7 | 5080 | 7558 | 320 |
3×300 | 741 | 1 | 0.095 | 2.4 | 0.235 | 6.0 | 2.56 | 65.0 | 6080 | 9046 | 357 |
3×350 | 855 | 1 | 0.095 | 2.4 | 0.235 | 6.0 | 2.68 | 68.1 | 7140 | 10623 | 394 |
3×400 | 988 | 1/0 | 0.095 | 2.4 | 0.250 | 6.4 | 2.82 | 71.6 | 7780 | 11575 | 430 |
3×500 | 1221 | 2/0 | 0.095 | 2.4 | 0.250 | 6.4 | 3.03 | 77.0 | 9065 | 13487 | 487 |
Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.