ICEA S-75-381 Type W Three-Conductor Round Portable Power Cable 2kV
APPLICATIONThis cable uses EPR insulation and a CPE jacket to ensure stable performance in high-temperature and high-abrasion environments, making it particularly suitable for harsh environments such as mining and construction sites.STANDARDSICEA S-75…
Type W Three-Conductor Round Portable Power Cable 2kV.pdf Contact us
  • APPLICATION

  • This cable uses EPR insulation and a CPE jacket to ensure stable performance in high-temperature and high-abrasion environments, making it particularly suitable for harsh environments such as mining and construction sites.

    STANDARDS

  • ICEA S-75-381/NEMA WC 58

  • ASTM B 172

  • ASTM B 33

  • CAN/CSA C22.2 No. 96

  • CONSTRUCTION

  • ConductorsStranded annealed tinned copper conductor.
    InsulationEthylene Propylene Rubber (EPR).
    JacketReinforced heavy-duty/extra-heavy-duty Chlorinated Polyethylene (CPE), black. (Cables having a nominal outside diameter of more than 2.0 inches require extra-heavy-duty jackets.)
  • OPTIONS

  • Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.
    Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.

  • MECHANICAL AND THERMAL PROPERTIES

  • Minimum Bending Radius6×OD
    Maximum Conductor Operating Temperature+90℃
  • DIMENSIONS AND WEIGHT

  • ConstructionNo. of StrandsNominal Insulation ThicknessNominal Jacket ThicknessNominal Overall DiameterNominal WeightAmpacity
    No. of cores × AWG/kcmil-inchmminchmminchmmlbs/kftkg/kmA
    3×81330.061.50.1253.20.9123.155081859
    3×61330.061.50.1403.61.0125.7730108679
    3×42590.061.50.1553.91.1729.710201518104
    3×22590.061.50.1553.91.3434.014302128138
    3×12590.082.00.1704.31.5138.418002678161
    3×1/02660.082.00.1704.31.6541.921403184186
    3×2/03420.082.00.1904.81.7544.525803839215
    3×3/04180.082.00.1904.81.8948.029224347249
    3×4/05320.082.00.2055.22.0451.838005654287
    3×2507410.0952.40.2205.62.3960.743686500320
    3×3508880.0952.40.2356.02.6667.558958772394
    3×50012210.0952.40.2506.42.9875.8782011638487
  • Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.