600/1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables to IEC 60502 (2-5 Cores & Multicore)
APPLICATIONThe cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. STANDARDSBasic design adapted to IEC 60502-1FIRE PERFORMANCEFlame Retardan…
600_1000V XLPE Insulated, PVC Sheathed, Armoured PowerCables to IEC 60502 (2-5&Multicore).pdf Contact us

APPLICATION

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. 

STANDARDS

Basic design adapted to IEC 60502-1

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)IEC 60332-1

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

ConductorAnnealed copper wire, stranded according to IEC 60228 class 2.
InsulationXLPE according to IEC 60502-1.
Inner CoveringExtruded PVC or polymeric compound.
ArmouringGalvanized steel wire
Outer SheathExtruded PVC Type ST1/ST2 according to IEC 60502-1.
Outer Sheath OptionUV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation ColourTwo-core: Brown, blue
Three-core: Brown, black, grey
Four-core: Blue, brown, black, grey
Five-core: Green-and-yellow, blue, brown, black, grey
Other colours can be offered upon request.
Sheath ColourBlack, other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation80°C (For ST1 Sheath); 90°C (For ST2 Sheath)
Maximum short circuit temperature (5 Seconds)250°C
Minimum bending radius12 x Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFLP600-RVMV-R
No. of Cores x Cross SectionClass of ConductorNominal
Insulation Thickness 
Nominal Inner
Covering Thickness
Nominal
Armour Wire Diameter
Nominal
Sheath Thickness
Nominal
Overall Diameter
Approx. Weight
No.xmm2 mm mmmm mmkg/km
2 Cores
2x1.520.71.00.91.813.2325
2x2.520.71.00.91.814.0372
2x4.020.71.00.91.815.1438
2x6.020.71.01.251.817.1645
2x1020.71.01.251.819.0806
2x1620.71.01.251.821.11015
2x2520.91.01.61.825.21517
2x3520.91.01.61.827.51830
2x5021.01.01.61.930.82259
2x7021.11.02.02.035.83182
2x9521.11.22.02.140.24022
2x12021.21.22.02.344.24810
2x15021.41.22.52.449.36120
2x18521.61.42.52.654.77375
2x24021.71.42.52.760.59037
2x30021.81.62.52.966.610871
2x40022.01.62.53.173.713256
3 Cores
3x1.520.71.00.91.813.6361
3x2.520.71.00.91.814.5420
3x4.020.71.00.91.815.7505
3x6.020.71.01.251.817.8742
3x1020.71.01.251.819.8954
3x1620.71.01.251.822.11231
3x2520.91.01.61.826.51857
3x3520.91.01.61.829.02281
3x5021.01.01.61.932.52856
3x7021.11.02.02.138.04056
3x9521.11.22.02.242.75196
3x12021.21.22.02.346.86247
3x15021.41.42.52.552.88000
3x18521.61.42.52.758.19626
3x24021.71.42.52.864.311939
3x30021.81.62.53.070.814468
3x40022.01.63.23.380.018832
3 Cores+1 Earth Conductor


power conductorearth  conductor




3x16/1020.70.71.01.61.822.71446
3x25/1620.90.71.01.61.826.51925
3x35/1620.90.71.01.61.929.02607
3x50/2521.00.91.01.62.133.03413
3x70/3521.10.91.22.02.238.04710
3x95/5021.11.01.22.02.342.46179
3x120/7021.21.11.22.02.548.08195
3x150/7021.41.11.42.52.752.010304
3x185/9521.61.11.42.52.857.213172
3x240/12021.71.21.62.53.164.016711
3x300/15021.81.41.62.53.269.821094
3x400/18522.01.61.63.23.678.627130
4 Cores
4x1.520.71.00.91.814.4406
4x2.520.71.00.91.815.4479
4x4.020.71.01.251.817.6718
4x6.020.71.01.251.819.0859
4x1020.71.01.251.821.31124
4x1620.71.01.61.824.51628
4x2520.91.01.61.828.62237
4x3520.91.01.61.931.62794
4x5021.01.02.02.136.53813
4x7021.11.22.02.241.95065
4x9521.11.22.02.346.76463
4x12021.21.42.52.552.98401
4x15021.41.42.52.758.09987
4x18521.61.42.52.863.712040
4x24021.71.62.53.171.515186
4x30021.81.62.53.278.018316
4x40022.01.83.23.688.723930
5 Cores
5x1.520.71.00.91.815.5467
5x2.520.71.00.91.816.6558
5x4.020.71.00.91.818.1692
5x6.020.71.01.251.820.3972
5x1020.71.01.251.822.81300
5x1620.71.01.61.826.41899
5x2520.91.01.61.931.22671
5x3520.91.01.62.034.53371
Multicore
7C1.520.71.00.91.816.4540
8C1.520.71.00.91.818.0692
10C1.520.71.01.251.820.1819
12C1.520.71.01.251.820.5882
19C1.520.71.01.251.823.11137
27C1.520.71.01.61.827.21618
37C1.520.71.01.61.829.71958
48C1.520.71.01.61.933.42378
7C2.520.71.01.251.817.6657
8C2.520.71.01.251.819.4834
10C2.520.71.01.251.821.7995
12C2.520.71.01.251.822.31082
19C2.520.71.01.61.825.21428
27C2.520.71.01.61.829.82033
37C2.520.71.01.61.832.72499
48C2.520.71.02.01.936.83063

Note: Other conductor sizes & core configurations are available upon request.

ELECTRICAL PROPERTIES

Conductor Operating Temperature90°C
Ambient Temperature30°C

Current-Carrying Capacities (Amp) according to BS7671:2008 table 4E4A

Conductor crosssectional
area
Reference Method C (clipped direct)Reference Method E (in free air
or on a perforated cable tray,
horizontal or vertical)
Reference Method D (direct in in
groud or in ducting in groud. in or
around buildings)
1 two-core cable*,
single-phase a.c.
or d.c.
1 three-or four
core cable*,
three-phase a.c.
1 two-core
cable*, singlephase
a.c. or
d.c.
1 three-or four
core cable*,
three-phase a.c.
1 two-core cable*,
single-phase a.c.
or d.c.
1 three-or four
core cable*, threephase
a.c.
1234567
mm2AAAAAA
1.5272329252521
2.5363139333328
4.0494252444336
6.0625366565344
10857390787158
1611094115999175
2514612415213111696
35180154188162139115
50219187228197164135
70279238291251203167
95338289354304239197
120392335410353271223
150451386472406306251
185515441539463343281
240607520636546395324
300698599732628446365
400787673847728--

Voltage Drop (Per Amp Per Meter) according to BS 7671: 2008 table 4E4B

Conductor cross- sectional areaTwo-core cables, d.c.Two-core cable, single-phase a.c.Three-or four core cable, three-phase a.c.
1234
mm2mV/A/mmV/A/mmV/A/m
1.5313127
2.5191916
4.0121210
6.07.97.96.8
104.74.74.0
162.92.92.5


rxzrxz
251.851.850.1601.901.600.1401.65
351.351.350.1551.351.150.1351.15
500.980.990.1551.000.860.1350.87
700.670.670.1500.690.590.1300.60
950.490.500.1500.520.430.1300.45
1200.390.400.1450.420.340.1300.37
1500.310.320.1450.350.380.1250.30
1850.250.260.1450.290.220.1250.26
2400.1950.2000.1400.240.1750.1250.21
3000.1550.1600.1400.210.1400.1200.185
4000.1200.1300.1400.1900.1150.1200.165

Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance