N2XSEYFGY MV Cables
ApplicationThe three core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 3.6/6KV to 18/30KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable d…
N2XSEYFGY 3.6-6 kV.pdf N2XSEYFGY 6-10 kV.pdf N2XSEYFGY 8.7-15 kV.pdf N2XSEYFGY 12-20 kV.pdf N2XSEYFGY 18-30 kV.pdf N2XSEYFGY 20.3-35 kV.pdf Contact us

Application

The three core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 3.6/6KV to 18/30KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

Standards

DIN VDE 0276 Part 620-622

HD 620 S1

Construction

Conductor : Stranded compacted circular copper or aluminium conductors according to IEC 60228 class 2 / VDE 0276 class 2 / VDE 0295 HD 383. All internal interstices of the conductor are filled with water blocking compound to prevent ingress of water through conductor during storage, handing, installation and operating of the cable.

Conductor Screen : The conductor screen consists of an extruded layer of non metallic, semi-conducting compound firmly bonded to the insulation to exclude all air voids. The screen has a minimum thickness of 0.3mm and the maximum volume resistivity of 500 Ohm-m at 90°C.

Insulation : Insulation is of extruded XLPE compound type 2XI1 according to DIN VDE 0207 part 22 and HD 620.1 with high degree of cross-linking, free from contaminants, air voids and heat resistant by dry cured process.

The nominal insulation wall thickness is shown in table 1.

Table 1. Insulation Thickness

Nom. Cross Section Area of ConductorInsulation Thickness at Nom. Voltage
3.6/6KV(Um=7.2KV)6/10KV(Um=12KV)8.7/15KV(Um=17.5KV)12/20KV(Um=24KV)18/30KV(Um=36KV)
mm²mmmmmmmmmm
352.53.44.55.5-
502.53.44.55.58.0
702.53.44.55.58.0
952.53.44.55.58.0
1202.53.44.55.58.0
1502.53.44.55.58.0
1852.53.44.55.58.0
2402.63.44.55.58.0
3002.83.44.55.58.0
4003.03.44.55.58.0

Insulation Screen : The insulation screen consists of extruded non metallic, semi-conducting compound extruded over the insulation. The extruded semi-conducting layer shall consist of bonded or cold strippable semi-conducting compound capable of removal for jointing or terminating.The minimum thickness is 0.3mm and the maximum volume resistivity of 500 Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and can be easily hand stripped on site.

Conducting Water Blocking Layer : The insulation screen may be coverd by semiconductive water blocking tape which will swell up under the influence of moisture of water to ensure longitudinal watertightness.

Metallic Layer : The metallic layer shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires. The metallic layer provides an earth fault current path, capable of withstanding fault current to earth of 1000A for one second at maximum temperature 160°C. Copper wires are applied over the conducting water blocking layer with a minimum diameter of 0.5mm. As an alternative, copper tape(s) with minimum thickness of 0.1mm can be applied with overlap. Total cross section of copper wire screen and copper tape screen layer are shown in Table 2a and 2b.

Table 2a. Total Cross Section and Max. DC Resistance of Copper Wire Screen

Nominal Cross-Section of CablesTotal Cross SectionMax. DC Resistance of Copper Wire Screen at 20℃
36/6KV (Um=7.2KV)6/10KV (Um=12KV)8.7/15KV (Um=17.5KV)12/20KV (Um=24KV)18/30KV (Um=36KV)
mm²mm²Ω
7016161616161.19
9516161616161.19
12016161616161.19
15025252525250.759
18525252525250.759
24025252525250.759
30025252525250.759
40035353535350.271
50035353535350.217
63035353535350.271

Table 2b. Total Cross Section and Max. DC Resistance of Copper Tape Screen (0.1mm)

Nominal Cross-Section of CablesTotal Cross Section & Max. DC Resistance
3.6/6KV(Um=7.2KV)6/10KV(Um=12KV)8.7/15KV(Um=17.5KV)12/20KV(Um=24KV)18/30KV(Um=36KV)
     
Total Cross SectionMax. DC Resistance at 20℃Total Cross SectionMax. DC Resistance at 20℃Total Cross SectionMax. DC Resistance at 20℃Total Cross SectionMax. DC Resistance at 20℃Total Cross SectionMax. DC Resistance at 20℃
mm²mm²Ωmm²Ωmm²Ωmm²Ωmm²Ω
706.62.6167.232.3808.022.1458.71.96710.51.075
957.32.3697.912.1748.711.9759.41.82411.21.075
1208.02.1538.641.9919.431.82310.21.69412.01.075
1508.52.0139.191.8719.991.72210.71.60612.50.688
1859.41.8389.881.74110.821.59011.41.50913.20.688
24010.41.65610.961.56911.761.46312.51.37814.30.688
30011.41.50811.841.45212.641.36113.41.28715.20.688
40012.61.36212.921.33213.711.25414.41.19216.20.491
50013.91.23714.341.19915.141.13615.51.11017.70.491
63015.31.12116.681.03116.571.03817.30.99519.10.491

Separator / Water Blocking Layer : The metallic screen may be covered by non-conducting water blocking tape which will swell up under the influence of moisture of water to ensure longitudinal watertightness.

Separation Sheath (for armoured cable) : The separation sheath comprises a layer of extruded PVC, PE or LSZH, applied under the armour. Thickness of separation sheath as shown in table 3.

Table 3. Separation Sheath Thickness

Core DiameterApprox.Thickess of Inner Sheath
mmmm
><
35451.4
45601.6
60801.8
80-2.0

Armour(for armoured cable) :

The armour consists of :

1) Double layers of galvanized steel tape are applied helically with proper inner overlapping over an extruded separation sheath. Thickness of the steel tape is shown in table 4.

Tabel 4. Galvanized Steel Tape Thickness

Inner DiameterThickness of Galvanized Steel Tape
mmmm
><
-300.2
30700.5
70-0.8

2) Galvanized flat steel wires with thickness of 0.8 mm are applied helically over the surface of inner sheath with minimum of 90% coverage. And galvanized Steel tape with nominal thickness of 0.3 mm is applied helically with 50% coverage to cover the surface of the flat wires.

Over Sheath : Overall sheath comprises a layer of extruded PE compound DMP2 according to HD620.1 and 2YM3 type to DIN VDE 0276 Part 3, or PVC compound DMV6 according to HD620.1 and YM5 to DIN VDE 0276 Part 6. LSZH can be offered as an option. Normal wall thickness is 2.5mm (for 1/500mmsq 18/30KV, wall thickness is 2.6mm), suitable for exposure to sun-light or other local atmospheric environments and for the operating temperature of the cable.

Physical Properties

Operating Temperature : up to 90°C

Temperature Range : -5°C ( PVC or LZSH sheath ); -20°C ( PE sheath )

Short Circuit Temperature : 250°C (short circuit duration up to 5 seconds)

Bending Radius : 15 x OD (Cable without metal sheath) ; 30 x OD (Cable with aluminium sheath)

Table 5. Nominal /Operating /Testing Voltages

Nominal Voltage Uo/UOperating Voltage (Um)Testing Voltage
3.6/6KV8KV12.5KV
6/10KV12KV21KV
8.7/15KV18KV30.5KV
12/20KV24KV42KV
18/30KV36KV63KV

TYPE CODES

Conductor

N - According to VDE Standard (No abbreviation for copper conductor)

A - Aluminium conductor

- - Copper conductor

Insulation

2X - XLPE

Screen

C - Concentric conductor of copper

CE - Concentric conductor of copper over each individual core

S - Screen of copper wires & copper tape, helically wound

SE - Screen of copper wires over each individual cores

(G) - Longitudinally waterproof

Armour

F - Armour of galvanized flat steel wire(strip)

Gb - Counter Helix of galvanized steel tape

B - Steel tape armouring

R - Armour of galvanized round steel wire

Ra - Armour of round aluminium wire

Sheath

2Y - PE

Y - PVC

H - LSZH

K - Lead sheath

KL - Aluminium sheath

Three Core 3.6/6KV (Um=7.2KV)

N2XSEY NA2XSEY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmkg/kmkg/km
256.052.515.11612.51.53721001600
357.102.516.31613.51.63925001800
508.252.517.81614.71.64230002100
709.902.519.71616.31.74638002500
9511.72.521.81618.11.75048003000
12013.12.524.01619.51.85358003500
15014.32.525.62520.71.85667003900
18516.32.528.12522.71.96081004600
24018.72.631.22525.31.966102005600
30020.92.834.22527.92.072125006700
40023.73.037.93531.12.180156008200

Three Core 3.6/6KV (Um=7.2KV) Galvanized Steel Tape Armoured Cables

N2XSEYBY NA2XSEYBY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Armour ThicknessNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmmmkg/kmkg/km
256.052.55.01612.50.52.23928002300
357.102.55.41613.50.52.34232002600
508.252.55.91614.70.52.44538002900
709.902.56.61616.30.52.54947003400
9511.72.57.31618.10.52.65358004000
12013.12.58.01619.50.52.75668004600
15014.32.58.52520.70.52.85979005100
18516.32.59.42522.70.82.96494005900
24018.72.610.42525.30.83.170117007000
30020.92.811.42527.90.83.376141008300
40023.73.012.63531.10.83.6851830010900

Three Core 3.6/6KV (Um=7.2KV) Galvanized Flat Steel Wire+Steel Tape Armoured Cables

N2XSEYFGbY NA2XSEYFGbY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Armour ThicknessNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmmmkg/kmkg/km
256.052.55.01612.50.82.24029002400
357.102.55.41613.70.82.34233002700
508.252.55.91614.70.82.44539003000
709.902.56.61616.30.82.54949003600
9511.72.57.31618.10.82.65360004200
12013.12.58.01619.50.82.75670004700
15014.32.58.52520.70.82.85981005200
18516.32.59.42522.70.82.96496006100
24018.72.610.42525.30.83.170119007200
30020.92.811.42527.90.83.376143008600
40023.73.012.63531.10.83.6841770010300

Electrical Data

Nom. Cross-Section AreaDC Resistance CU / ALAC Resistance CU / ALShort Circuit Rating of Conductor CU / AL 1 secCapacitanceCharging CurrentShort Circuit Rating of Copper Wire Screen Per Core 1 secShort Circuit Rating of Copper Tape Screen Per Core 1 secReactanceInductance
mm²µΩ/mµΩ/mkApF/mmA/mkAkAµΩ/mnH/m
25727/1200927/15383.6/2.32720.331.960.73116370
35524/868668/11135.0/3.23010.361.960.79108350
50387/641494/8226.8/4.43320.401.960.87102330
70268/443343/5689.8/6.33830.461.960.9697310
95193/320248/41013.3/8.54320.521.961.0692290
120153/253196/32517.2/11.04740.571.961.1789280
150124/206159/26521.2/13.55110.613.061.2587280
18599/164128/21126.6/17.05620.673.061.3786270
24075/12598/16134.9/22.36020.723.061.5283260
30060/10080/13043.8/28.06220.753.061.6782260
40047/7864/10257.3/36.66480.784.291.8480250

Three Core 6/10KV (Um=12KV)

N2XSEY NA2XSEY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmkg/kmkg/km
256.053.45.681614.31.64124001900
357.103.46.091615.31.64328002200
508.253.46.581616.51.74634002500
709.903.47.231618.11.75042002900
9511.73.47.911619.91.85453003400
12013.13.48.641621.31.85762003900
15014.33.49.192522.51.96072004400
18516.33.49.882524.51.96486005100
24018.73.410.962526.92.070107006100
30020.93.411.842529.12.175129007100
40023.73.412.923531.92.281159008500

Three Core 6/10KV (Um=12KV) Galvanized Steel Tape Armoured Cables

N2XSEYBY NA2XSEYBY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Armour ThicknessNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmmmkg/kmkg/km
256.053.45.681614.30.52.34432002700
357.103.46.091615.30.52.44637003000
508.253.46.581616.50.52.54943003400
709.903.47.231618.10.52.65352003900
9511.73.47.911619.90.52.85764004600
12013.13.48.641621.30.52.96174005200
15014.33.49.192522.50.53.06485005700
18516.33.49.882524.50.53.168100006500
24018.73.410.962526.90.53.374123007600
30020.93.411.842529.10.53.479146008800
40023.73.412.923531.90.83.7871870011300

Three Core 6/10KV (Um=12KV) Galvanized Flat Steel Wire+Steel Tape Armoured Cables

N2XSEYFGbY NA2XSEYFGbY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Armour ThicknessNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmmmkg/kmkg/km
256.053.45.681614.30.82.34433002800
357.103.46.091615.30.82.44638003100
508.253.46.581616.50.82.54944003500
709.903.47.231618.10.82.65354004100
9511.73.47.911619.90.82.85765004700
12013.13.48.641621.30.82.96176005300
15014.33.49.192522.50.83.06487005900
18516.33.49.882524.50.83.168102006800
24018.73.410.962526.90.83.374125007900
30020.93.411.842529.10.83.479149009100
40023.73.412.923531.90.83.7861800010600

Electrical Data

Nom. Cross-Section AreaDC Resistance CU / ALAC Resistance CU / ALShort Circuit Rating of Conductor CU / AL 1 secCapacitanceCharging CurrentShort Circuit Rating of Copper Wire Screen Per Core 1 secShort Circuit Rating of Copper Tape Screen Per Core 1 secReactanceInductance
mm²µΩ/mµΩ/mkApF/mmA/mkAkAµΩ/mnH/m
25727/1200927/15383.6/2.32040.431.960.83129405
35524/868668/11135.0/3.22370.471.960.89115370
50387/641494/8226.8/4.42600.521.960.96109350
70268/443343/5689.8/6.32980.601.961.05103330
95193/320248/41013.3/8.53340.671.961.1699320
120153/253196/32517.2/11.03650.731.961.2696310
150124/206159/26521.2/13.53920.783.061.3493300
18599/164128/21126.6/17.04300.863.061.4490290
24075/12598/16134.9/22.34760.953.061.6087280
30060/10080/13043.8/28.05241.053.061.7385270
40047/7864/10257.3/36.65801.164.291.8981260

Three Core 8.7/15KV (Um=17.5KV)

N2XSEY NA2XSEY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmkg/kmkg/km
256.054.56.471616.51.74635002400
357.104.56.891617.51.74838002600
508.254.57.371618.71.75144003000
709.904.58.021620.31.85553003400
9511.74.58.711622.11.85964004000
12013.14.59.431623.51.96274004500
15014.34.59.992524.71.96585005000
18516.34.510.822526.72.069100005800
24018.74.511.762529.12.175122006800
30020.94.512.642531.32.180144007900
40023.74.513.713534.12.287175009300

Three Core 8.7/15KV (Um=17.5KV) Galvanized Steel Tape Armoured Cables

N2XSEYBY NA2XSEYBY

Dimensional Data

Nom. Cross-Section AreaApprox Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox Insulation DiameterNom. Armour ThicknessNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmmmkg/kmkg/km
256.054.56.471616.50.52.54938003300
357.104.56.891617.50.52.65143003600
508.254.57.371618.70.52.75449004000
709.904.58.021620.30.52.85859004600
9511.74.58.711622.10.52.96271005300
12013.14.59.431623.50.53.06681005900
15014.34.59.992524.70.53.16992006400
18516.34.510.822526.70.53.374109007400
24018.74.511.762529.10.53.479131008500
30020.94.512.642531.30.53.6861640010600
40023.74.513.713534.10.83.9931970012300

Three Core 8.7/15KV (Um=17.5KV) Galvanized Flat Steel Wire+Steel Tape Armoured Cables

N2XSEYFGbY NA2XSEYFGbY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Armour ThicknessNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmmmkg/kmkg/km
256.054.56.471616.50.82.54934003400
357.104.56.891617.50.82.65144003800
508.254.57.371618.70.82.75451004200
709.904.58.021620.30.82.85860004700
9511.74.58.711622.10.82.96273005400
12013.14.59.431623.50.83.06683006100
15014.34.59.992524.70.83.16994006600
18516.34.510.822526.70.83.374111007600
24018.74.511.762529.10.83.479134008700
30020.94.512.642531.30.83.6851580010000
40023.74.513.713534.10.83.9911900011600

Electrical Data

Nom. Cross-Section AreaDC Resistance CU / ALAC Resistance CU / ALShort Circuit Rating of Conductor CU / AL 1 secCapacitanceCharging CurrentShort Circuit Rating of Copper Wire Screen Per Core 1 secShort Circuit Rating of Copper Tape Screen Per Core 1 secReactanceInductance
mm²µΩmµΩ/mkApF/mmA/mkAkAµΩmnH/m
25727/1200927/15383.6/2.31760.481.960.95132410
35524/868668/11135.0/3.21930.531.961.01123390
50387/641494/8226.8/4.42110.581.961.08116370
70268/443343/5689.8/6.32400.651.961.17110350
95193/320248/41013.3/8.52670.731.961.27105330
120153/253196/32517.2/11.02910.791.961.38102320
150124/206159/26521.2/13.53120.853.061.4698310
18599/164128/21126.6/17.03400.933.061.5895300
24075/12598/16134.9/22.33751.023.061.7291290
30060/10080/13043.8/28.04111.123.061.8589280
40047/7864/10257.3/36.64541.244.292.0084270

Three Core 12/20KV (Um=24KV)

N2XSEY NA2XSEY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmkg/kmkg/km
357.105.57.61619.71.85338003100
508.255.58.11620.91.85644003500
709.905.58.71622.51.96053004000
9511.75.59.41624.31.96464004600
12013.15.510.21625.72.06774005200
15014.35.510.72526.92.07085005700
18516.35.511.42528.92.175100006500
24018.75.512.52531.32.180122007500
30020.95.513.42533.52.285144008700
40023.75.514.43536.32.3911750010200

Three Core 12/20KV (Um=24KV) Galvanized Steel Tape Armoured Cables

N2XSEYBY NA2XSEYBY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Armour ThicknessNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmmmkg/kmkg/km
357.105.57.61619.70.52.75749004200
508.255.58.11620.90.52.96056004700
709.905.58.71622.50.53.06466005300
9511.75.59.41624.30.53.16878006000
12013.15.510.21625.70.53.27189006600
15014.35.510.72526.90.53.374101007200
18516.35.511.42528.90.53.479117008200
24018.75.512.52531.30.83.6861490010200
30020.95.513.42533.50.83.8911740011600
40023.75.514.43536.30.84.0982080013400

Three Core 12/20KV (Um=24KV) Galvanized Flat Steel Wire+Steel Tape Armoured Cables

N2XSEYFGbY NA2XSEYFGbY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Armour ThicknessNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmmmkg/kmkg/km
357.105.57.61619.70.82.75750004400
508.255.58.11620.90.82.96057004800
709.905.58.71622.50.83.06468005400
9511.75.59.41624.30.83.16880006200
12013.15.510.21625.70.83.27191006800
15014.35.510.72526.90.83.374103007500
18516.35.511.42528.90.83.479119008400
24018.75.512.52531.30.83.685143009600
30020.95.513.42533.50.83.8901670010900
40023.75.514.43536.30.84.0972010012700

Electrical Data

Nom. Cross-Section AreaDC Resistance CU / ALAC Resistance CU / ALShort Circuit Rating of Conductor CU / AL 1 secCapacitanceCharging CurrentShort Circuit Rating of Copper Wire Screen Per Core 1 secShort Circuit Rating of Copper Tape Screen Per Core 1 secReactanceInductance
mm²µΩ/mµΩ/mkApF/mmA/mkAkAµΩ/mnH/m
35524/868668/11135.0/3.21680.671.961.11129410
50387/641494/8226.8/4.41830.731.961.18122390
70268/443343/5689.8/6.32070.831.961.28115370
95193/320248/41013.3/8.52290.921.961.38110350
120153/253196/32517.2/11.02491.001.961.48106340
150124/206159/26521.2/13.52661.063.061.56103330
18599/164128/21126.6/17.02891.163.061.66100320
24075/12598/16134.9/22.33181.273.061.8295300
30060/10080/13043.8/28.03481.393.061.9593300
40047/7864/10257.3/36.63881.534.292.1187280

Three Core 18/30KV (Um=36KV)

N2XSEY NA2XSEY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmkg/kmkg/km
508.258.09.91625.92.06858004900
709.908.010.51627.52.07168005500
9511.78.011.21629.32.17580006100
12013.18.012.01630.72.17990006700
15014.38.012.52531.92.281101007300
18516.38.013.22533.92.286118008300
24018.78.014.32536.32.391140009400
30020.98.015.22538.52.4971650010700
40023.78.016.23541.32.51031970012300

Three Core 18/30KV (Um=36KV) Galvanized Steel Tape Armoured Cables

N2XSEYBY NA2XSEYBY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Armour ThicknessNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmmmkg/kmkg/km
508.258.09.91625.90.53.27273006400
709.908.010.51627.50.53.37584007100
9511.78.011.21629.30.53.58097007900
12013.18.012.01630.70.83.684117009400
15014.38.012.52531.90.83.7871290010100
18516.38.013.22533.90.83.9921480011300
24018.78.014.32536.30.84.0981730012600
30020.98.015.22538.50.84.21032000014100
40023.78.016.23541.30.84.41102350016000

Three Core 18/30KV (Um=36KV) Galvanized Flat Steel Wire+Steel Tape Armoured Cables

N2XSEYFGbY NA2XSEYFGbY

Dimensional Data

Nom. Cross-Section AreaApprox. Conductor DiameterNom. Insulation ThicknessCopper Tape Screen Area (0.1mm)Copper Wire Screen AreaApprox. Insulation DiameterNom. Armour ThicknessNom. Sheath ThicknessApprox. Overall DiameterApprox. Weight
CUAL
mm²mmmmmm²mm²mmmmmmmmkg/kmkg/km
508.258.09.91625.90.83.27275006600
709.908.010.51627.50.83.37686007300
9511.78.011.21629.30.83.580100008100
12013.18.012.01630.70.83.683112008900
15014.38.012.52531.90.83.786124009500
18516.38.013.22533.90.83.9911410010600
24018.78.014.32536.30.84.0971660011900
30020.98.015.22538.50.84.21021920013400
40023.78.016.23541.30.84.41092270015300

Electrical Data

Nom. Cross-Section AreaDC Resistance CU / ALAC Resistance CU / ALShort Circuit Rating of Conductor CU / AL 1 secCapacitanceCharging CurrentShort Circuit Rating of Copper Wire Screen Per Core 1 secShort Circuit Rating of Copper Tape Screen Per Core 1 secReactanceInductance
mm²µΩ/mµΩ/mkApF/mmA/mkAkAµΩ/mnH/m
50387/641494/8226.8/4.41420.851.961.45134430
70268/443343/5689.8/6.31590.951.961.54127400
95193/320248/41013.3/8.51751.051.961.64121390
120153/253196/32517.2/11.01891.131.961.75117370
150124/206159/26521.2/13.52011.213.061.83113360
18599/164128/21126.6/17.02171.33.061.93109350
24075/12598/16134.9/22.32371.423.062.09104330
30060/10080/13043.8/28.02581.553.062.21101320
40047/7864/10257.3/36.62821.694.292.3796290

Current Rating for Three Core 1.8/3KV(Um=7.2KV ) to 26/35KV(Um=42KV) XLPE Insulation

 UnarmoredArmored
Nom. Cross-Section AreaBuried direct in GroundLaid in Single Way DuctLaid in AirBuried direct in GroundLaid in Single Way DuctLaid in Air
CUALCUALCUALCUALCUALCUAL
mm²AAAAAA
10765362428762765363438863
161017887671098410178886811085
251291001128714211012910011287143111
35153119133103170132154119134104172133
50181140158122204158181140158123205159
70221171193150253196220171194150253196
95262203231179304236263204232180307238
120298232264205351273298232264206352274
150334260297231398309332259296231397309
185377294336262455355374293335262453354
240434340390305531415431338387304529415
300489384441346606475482380435343599472
400553438501398696552541432492393683545
500613498541451786652601492532446773645
630663568591501896762651562582496883755