CAT.5e Outdoor
LSZH Flame Retardant CAT5E CWB/SWB/SWA Armoured Data CablesFTX-CAT5EU/UTP4P24LH CWB/SWB/SWAFTX-CAT5EF/UTP4P24LH CWB/SWB/SWAFTX-CAT5ESF/UTP4P24LH CWB/SWB/SWAAPPLICATIONCat5E is a cable standard for Gigabit Ethernet and other network protocol, suitable …
CAT. 5e Outdoor.pdf Contact us

LSZH Flame Retardant CAT5E CWB/SWB/SWA Armoured Data Cables

FTX-CAT5EU/UTP4P24LH CWB/SWB/SWA

FTX-CAT5EF/UTP4P24LH CWB/SWB/SWA

FTX-CAT5ESF/UTP4P24LH CWB/SWB/SWA


APPLICATION

Cat5E is a cable standard for Gigabit Ethernet and other network protocol, suitable for basic voice and data installations up to 100 MHz. In addition, these cables can be offered with copper wire braid armoured & flame retardant outer sheath, providing additional mechanically protection still maintaining the flexibility of the cable.

STANDARDS

ISO/IEC 11801 , EN 50173 , ANSI/TIA/EIA 568

FIRE PERFORMANCE

Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2
Minimum Smoke EmissionIEC 61034-2; EN 61034-2

CABLE CONSTRUCTION

Conductors : 24AWG solid bare copper.

Insulation : PE.

Twinning : Two coloured insulated conductors twisted together to form a pair.

Inner Sheath : Thermoplastic LSZH compound.

Armouring :

CWB : Copper Wire Braid

SWB : Steel Wire Braid

SWA : Steel Wire Armour

Outer Sheath : Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered).

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

Cat5EF/UTP : These cables have collective shielding of Aluminium/polyester tape with drain wire.

Cat5ESF/UTP : These cables have double collective shielding of Aluminium/polyester tape & copper wire braid.

PHYSICAL AND THERMAL PROPERTIES

Temperature range : -30°C - +75°C

Minimum bending radius during installation (mobile state) : 8 x Overall Diameter

Minimum bending radius during operation (fixed state) : 4 x Overall Diameter

ELECTRICAL PROPERTIES

AWG 24
Nominal Conductor Diametermm0.50/0.51/0.53
Maximum DC Resistance@20°CΩ/100m9.38
Maximum DCR Unbalance%5
Maximum Mutual CapacitancepF/m55.8
Maximum Capacitance UnbalancepF/100m330
Characteristic Impedance@1-100MHzΩ100±15
Maximum Propagation Delay Skewns/100m45

TRANSMISSION PROPERTIES

FREQAttenuationNEXTPSNEXTELFEXTPSELFEXTRL
MHzdB/100mdBdBdB/100mdB/100mdB
0.7721.867.064.066.063.0
12.065.362.363.860.820.0
44.156.353.351.748.723.0
85.851.848.845.742.724.5
106.550.347.343.840.825.0
168.247.344.339.736.725.0
209.345.842.837.734.725.0
2510.444.341.335.832.824.3
31.2511.742.939.933.930.923.6
62.517.038.435.427.824.821.5
10022.035.332.323.820.820.1

CONSTRUCTION PARAMETERS

Cable CodeConstruction No. of Elements×No. of Cores in Element×Conductor DiameterNominal Insulation ThicknessNominal Inner Sheath ThicknessNominal Outer Sheath ThicknessAprrox. Overall DiameterNominal Weight
mmmmmmmmmmkg/km
CAT5EU/UTP4P24LH CWB4×2×0.50.20.61.07.68102
CAT5EU/UTP4P24LH SWB4×2×0.50.20.61.07.6898
CAT5EU/UTP4P24LH SWA4×2×0.50.20.61.08.68170
CAT5EF/UTP4P24LH CWB4×2×0.530.20.61.08.28121
CAT5EF/UTP4P24LH SWB4×2×0.530.20.61.08.28117
CAT5EF/UTP4P24LH SWA4×2×0.530.20.61.09.28197
CAT5ESF/UTP4P24LH CWB4×2×0.530.20.61.08.76128
CAT5ESF/UTP4P24LH SWB4×2×0.530.20.61.08.76124
CAT5ESF/UTP4P24LH SWA4×2×0.530.20.61.09.76221