RE-2Y(St)Y Multi-Core
PE Insulated, PVC Sheathed & Overall Screened Instrumentation Cables (Multicore)APPLICATIONFor transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79…
RE-2Y(St)Y-fl RE-2Y(St)Yv-fl Multi-Core.pdf Contact us

PE Insulated, PVC Sheathed & Overall Screened Instrumentation Cables (Multicore)

APPLICATION

For transmission of analogue and digital signals in instrument and control systems; allowed for use in zone 1 and zone 2, group II, classified areas (IEC 79-14), not allowed for direct connection to low impedance sources, e.g. public mains electricity supply. Recommended for indoor and outerdoor installation, on racks, trays, in conduits, in dry and wet locations; not for direct buiral. Recommended for use as fire protection messure for people and important material assets.

STANDARDS

Basic design to EN 50288-7

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires& cable test)***EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen FreeIEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke EmissionIEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gasesNES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard, *** denotes optional.

VOLTAGE RATING

500V

CABLE CONSTRUCTION

  • Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

  • Insulation: PE compound as per EN 50290. 2-23.

  • Overall Screen: Aluminium/polyester tape with 0.5mm2 screen (7/0.3mm) tinned copper drain wire.

  • Outer Sheath: Thermoplastic PVC compound as per EN 50290-2-22. UV resistance, hydrocarbon< resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

  • Insulation: Black numbered
    Outer Sheath: Black, blue for intrinsically safe systems

PHYSICAL and THERMAL PROPERTIES

  • Temperature Range During Operation (Fixed State): -30°C – +70°C

  • Temperature Range During Installation (Mobile State): -5°C – +50°C

  • Minimum Bending Radius: 7.5 X Overall Diameter

  • Sunlight Resistance: UL 1581 section 1200

  • Oil Resistance: ICEA S-73-532(Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation)

ELECTRICAL ROPERTIES

CONDUCTOR AREA SIZEMM20.50.751.01.31.52.5
INSULATION THICKNESS (NOMINAL)MM0.550.550.550.60.60.7
CONDUCTOR RESISTANCE (20°C)Ω/KM36.725.018.514.212.37.4
INSULATION RESISTANCE (20°C)MΩ.KM(MIN.)5000
MUTUAL CAPACITANCE (1 KHZ)PF/M(MAX.)115
CAPACITANCE UNBALANCE(1 KHZ)PF/500 M (MAX.)500
L / R (RATIO) (MAX.)ΜH/Ω252525404060
OPERATING VOLTAGEV500
TEST VOLTAGE URMSCORE TO COREV2000
CORE TO SCREENV2000

CONSTRUCTION PARAMETERS

CALEDONIAN CABLE CODERE-2Y(ST)Y
NO. OF CORES X1XCROSS SECTIONNOMINALINSULATION THICKNESSNOMINALOUTER SHEATH THICKNESSNOMINALOVERALL DIAMETERAPPROX. WEIGHT
 NO.X1XMM2MMMMMMKG/KM
0.5mm2, Multicore
RE-2Y(St)Y 2C0.52x1x0.50.550.96.245
RE-2Y(St)Y 3C0.53x1x0.50.550.96.553
RE-2Y(St)Y 4C0.54x1x0.50.550.97.060
RE-2Y(St)Y 5C0.55x1x0.50.550.97.671
RE-2Y(St)Y 8C0.58x1x0.50.551.09.195
RE-2Y(St)Y 10C0.510x1x0.50.551.010.4122
RE-2Y(St)Y 12C0.512x1x0.50.551.010.7145
RE-2Y(St)Y 14C0.514x1x0.50.551.011.3162
RE-2Y(St)Y 16C0.516x1x0.50.551.111.8180
RE-2Y(St)Y 20C0.520x1x0.50.551.113.3214
RE-2Y(St)Y 24C0.524x1x0.50.551.114.7258
RE-2Y(St)Y 27C0.527x1x0.50.551.215.0282
RE-2Y(St)Y 30C0.530x1x0.50.551.215.7308
RE-2Y(St)Y 37C0.537x1x0.50.551.216.9372
RE-2Y(St)Y 40C0.540x1x0.50.551.217.6398
0.75mm2, Multicore
RE-2Y(St)Y 2C0.752x1x0.750.550.96.5165
RE-2Y(St)Y 3C0.753x1x0.750.550.96.9?232
RE-2Y(St)Y 4C0.754x1x0.750.550.97.4300
RE-2Y(St)Y 5C0.755x1x0.750.550.98.1382
RE-2Y(St)Y 8C0.758x1x0.750.551.09.7?579
RE-2Y(St)Y 10C0.7510x1x0.750.551.011.1?730
RE-2Y(St)Y 12C0.7512x1x0.750.551.011.5?870
RE-2Y(St)Y 14C0.7514x1x0.750.551.112.2?1007
RE-2Y(St)Y 16C0.7516x1x0.750.551.112.9?1148
RE-2Y(St)Y 20C0.7520x1x0.750.551.114.3?1431
RE-2Y(St)Y 24C0.7524x1x0.750.551.216.0?1705
RE-2Y(St)Y 27C0.7527x1x0.750.551.216.3?1916
RE-2Y(St)Y 30C0.7530x1x0.750.551.216.9?2122
RE-2Y(St)Y 37C0.7537x1x0.750.551.218.2?2601
RE-2Y(St)Y 40C0.7540x1x0.750.551.319.1?2816
1.0mm2, Multicore
RE-2Y(St)Y 2C1.02x1x1.00.550.96.958
RE-2Y(St)Y 3C1.03x1x1.00.550.97.370
RE-2Y(St)Y 4C1.04x1x1.00.550.97.985
RE-2Y(St)Y 5C1.05x1x1.00.550.98.698
RE-2Y(St)Y 8C1.08x1x1.00.551.010.3136
RE-2Y(St)Y 10C1.010x1x1.00.551.011.9194
RE-2Y(St)Y 12C1.012x1x1.00.551.012.2214
RE-2Y(St)Y 14C1.014x1x1.00.551.113.0243
RE-2Y(St)Y 16C1.016x1x1.00.551.113.7280
RE-2Y(St)Y 20C1.020x1x1.00.551.115.2336
RE-2Y(St)Y 24C1.024x1x1.00.551.217.0404
RE-2Y(St)Y 27C1.027x1x1.00.551.217.4443
RE-2Y(St)Y 30C1.030x1x1.00.551.218.0484
RE-2Y(St)Y 37C1.037x1x1.00.551.219.6590
RE-2Y(St)Y 40C1.040x1x1.00.551.320.4632
1.3mm2, Multicore
RE-2Y(St)Y 2C1.32x1x1.30.60.97.472
RE-2Y(St)Y 3C1.33x1x1.30.60.97.986
RE-2Y(St)Y 4C1.34x1x1.30.60.98.5105
RE-2Y(St)Y 5C1.35x1x1.30.61.09.5135
RE-2Y(St)Y 8C1.38x1x1.30.61.011.2176
RE-2Y(St)Y 10C1.310x1x1.30.61.113.2228
RE-2Y(St)Y 12C1.312x1x1.30.61.113.6269
RE-2Y(St)Y 14C1.314x1x1.30.61.114.3305
RE-2Y(St)Y 16C1.316x1x1.30.61.115.0351
RE-2Y(St)Y 20C1.320x1x1.30.61.216.9423
RE-2Y(St)Y 24C1.324x1x1.30.61.218.7507
RE-2Y(St)Y 27C1.327x1x1.30.61.319.3558
RE-2Y(St)Y 30C1.330x1x1.30.61.320.0611
RE-2Y(St)Y 37C1.337x1x1.30.61.321.6743
RE-2Y(St)Y 40C1.340x1x1.30.61.422.7796
1.5mm2, Multicore
RE-2Y(St)Y 2C1.52x1x1.50.60.97.778
RE-2Y(St)Y 3C1.53x1x1.50.60.98.194
RE-2Y(St)Y 4C1.54x1x1.50.60.98.8116
RE-2Y(St)Y 5C1.55x1x1.50.61.09.8149
RE-2Y(St)Y 8C1.58x1x1.50.61.011.6196
RE-2Y(St)Y 10C1.510x1x1.50.61.113.7261
RE-2Y(St)Y 12C1.512x1x1.50.61.114.1300
RE-2Y(St)Y 14C1.514x1x1.50.61.114.8340
RE-2Y(St)Y 16C1.516x1x1.50.61.115.6392
RE-2Y(St)Y 20C1.520x1x1.50.61.217.6474
RE-2Y(St)Y 24C1.524x1x1.50.61.319.6567
RE-2Y(St)Y 27C1.527x1x1.50.61.320.1625
RE-2Y(St)Y 30C1.530x1x1.50.61.320.8685
RE-2Y(St)Y 37C1.537x1x1.50.61.422.6834
RE-2Y(St)Y 40C1.540x1x1.50.61.423.6898
2.52, Multicore
RE-2Y(St)Y 2C2.52x1x2.50.70.98.9113
RE-2Y(St)Y 3C2.53x1x2.50.71.09.7145
RE-2Y(St)Y 4C2.54x1x2.50.71.010.5178
RE-2Y(St)Y 5C2.55x1x2.50.71.011.9285
RE-2Y(St)Y 8C2.58x1x2.50.71.113.9376
RE-2Y(St)Y 10C2.510x1x2.50.71.216.3426
RE-2Y(St)Y 12C2.512x1x2.50.71.216.9537
RE-2Y(St)Y 14C2.514x1x2.50.71.217.7609
RE-2Y(St)Y 16C2.516x1x2.50.71.318.9711
RE-2Y(St)Y 20C2.520x1x2.50.71.321.1826
RE-2Y(St)Y 24C2.524x1x2.50.71.423.6930
RE-2Y(St)Y 27C2.527x1x2.50.71.424.11040
RE-2Y(St)Y 30C2.530x1x2.50.71.525.21142
RE-2Y(St)Y 37C2.537x1x2.50.71.527.21392
RE-2Y(St)Y 40C2.540x1x2.50.71.628.51494

Note : Other conductor sizes & core configurations are available upon request.