The cables is mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
Basic design adapted to BS7211
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482- 332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic Gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
600/1000V
Conductor: Plain annealed copper wire, stranded according to IEC 60228 class 2. Insulation: LSZH compound.
Insulation Colour : Natural Sheath Colour: Black (other colors upon request)
Temperature Range During Operation: -30°C ~ 90°C Temperature Range during Installation : -5°C ~ 50°C Minimum Bending Radius: 6 x OD
Dielectric Test: | 3500 V r.m.s. x 5’ ( core / core ) |
Insulation Resistance | 500 MΩ x km ( at 20°C ) |
Short circuit Temperature | 250°C ( up to 5 secs ) |