H07V-K Cable
Application and DescriptionThese are not suitable to be installed for laying in tubes, under and surface mounting of plaster and also in closed installation conduits.These are not allowed to install for direct laying on cable trays, channel or tanks. …
H07V-K.pdf Contact us

Application and Description

These are not suitable to be installed for laying in tubes, under and surface mounting of plaster and also in closed installation conduits.

These are not allowed to install for direct laying on cable trays, channel or tanks. These types are permitted for the inner wiring of equipment, distributor and switchboards and also for protective laying to the lightings with a nominal voltage up to 1000 V alternating current or up to 750 V direct current against earth.

Standard and Approval

  • NF C 32-201-3

  • CE Low Voltage Directive 73/23/EEC and 93/68/EEC

  • ROHS compliant

Cable Construction

Fine bare copper strands
Strands to VDE-0295 Class-5, IEC 60228 Class-5
Special PVC TI1 core insulation
Cores to VDE-0293 colors on chart

Technical Characteristics

WORKING VOLTAGE450/750V
TEST VOLTAGE2500 volts
FLEXING BENDING RADIUS12.5 x Ø
STATIC BENDING RADIUS12.5 x Ø
FLEXING TEMPERATURE-5º C to +70º C
STATIC TEMPERATURE-30º C to +80º C
SHORT CIRCUIT TEMPERATURE+160º C
FLAME RETARDANTNF C 32-070
INSULATION RESISTANCE10 MΩ x km