N2XSY 3.6/6 kV MV cables
6.35/11kV XLPE Insulated, MDPE Sheathed, Armoured MV Power Cables (Single Core)N2XSYB2Y (CU/XLPE/CS/PVC/ATA/PE 6.35/11kV Class 2)N2XSYR2Y (CU/XLPE/CS/PVC/AWA/PE 6.35/11kV Class 2)
N2XSY 3.6-6 kV.pdf Contact us

6.35/11kV XLPE Insulated, MDPE Sheathed, Armoured MV Power Cables (Single Core)

N2XSYB2Y (CU/XLPE/CS/PVC/ATA/PE 6.35/11kV Class 2)

N2XSYR2Y (CU/XLPE/CS/PVC/AWA/PE 6.35/11kV Class 2)


Application

They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

Standards

Basic design adapted to IEC 60502-2

Construction

Conductor : Plain annealed copper wire, stranded according to IEC/BS EN 60228 class 2..

Conductor Screen : Extruded layer of semi-conducting cross-linkable compound is applied over the conductor and shall cover the surface completely.

Insulation : Extruded cross-linked compound type (XLPE)

Insulaton Screen : Extruded layer of semi-conducting cross-linkable compound is applied over the insulation.

Metallic Screen : The metallic layer shall be applied as a collective screen. The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires.

Separation Sheath : Thermoplastic PVC compound.

Armour : Aluminium tape or Aluminium wire.

Outer Sheath : Thermoplastic MDPE compound Type ST7 according to IEC 60502-2.The overall cable design will be more suitable for wet locations.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance and anti-rodent can be offered as option.

COLOUR CODE

Insulation Colour : Natural colouring.

Sheath Colour : Red

PHYSICAL PROPERTIES

Operating Temperature : up to 90°C

Temperature Range: -5°C

Short Circuit Temperature( 5 seconds maximum duration ) : 250°C

Bending Radius : 20 x OD

Nominal /Operating /Testing Voltages

Rated Voltage Uo/UOperating Voltage (Um)Testing Voltage (rms)
6.35/11KV12KV25.5KV

DIMENSIONAL DATA

N2XSYB2Y (CU/XLPE/CS/PVC/ATA/PE 6.35/11kV Class 2)

Nom. Cross-Section AreaNom. Insulation ThicknessCopper Wire Screen AreaCopper Tape Screen AreaNom. Bedding ThicknessNom. Armour Tape ThicknessNom.Sheath ThicknessApprox. Overall DiameterApprox. Weight
mm²mmmm²mm²mmmmmmmmkg/km
703.4168.21.20.51.930.87590
953.4168.91.20.51.932.46240
1203.4169.81.20.52.034.05150
1503.42510.41.20.52.136.74160
1853.42511.21.20.52.137.43260
2403.42512.41.20.52.240.13010
3003.42513.41.20.52.242.12650
4003.43514.61.20.52.446.22214
5003.43516.21.30.52.549.02020
6303.43518.91.40.52.654.41700

N2XSYR2Y (CU/XLPE/CS/PVC/AWA/PE 6.35/11kV Class 2)

Nom. Cross-Section AreaNom. Insulation ThicknessCopper Wire Screen AreaCopper Tape Screen AreaNom. Bedding ThicknessNom. Armour Wire DiameterNom.Sheath ThicknessApprox. Overall DiameterApprox. Weight
mm²mmmm²mm²mmmmmmmmkg/km
703.4168.21.21.61.932.08230
953.4168.91.21.61.933.66780
1203.4169.81.21.62.035.25589
1503.42510.41.21.62.137.94490
1853.42511.21.22.02.139.43490
2403.42512.41.22.02.242.13240
3003.42513.41.22.02.244.12870
4003.43514.61.22.02.448.22430
5003.43516.21.32.52.552.02130
6303.43518.91.42.52.657.41840

ELECTRICAL DATA

Nom. Cross- Section AreaD C ResistanceA C ResistanceShort Circuit Rating of Conductor 1 secCapacitanceCharging CurrentShort Circuit Rating of Screen 1 secReactanceInductanceImpedance
Copper WireCopper TapeTrefoilFlat SpacedTrefoilFlat SpacedTrefoilFlat Spaced
mm²µΩ/mµΩ/mkApF/mmA/mkAµΩ/mµΩ/mnH/mnH/mµΩ/mµΩ/m
702683439.82880.581.961.19122188390600364386
9519324813.33230.651.961.31122182390580272300
12015319617.23530.711.961.43116172370550225257
15012415921.23800.763.061.52110166350530193229
1859912826.64160.833.061.63107166340530165206
240759834.94600.923.061.81104163330520140185
300608043.85061.013.061.95100157320500126174
400476457.35611.124.292.1394154300490113164
500375172.36191.244.292.3791151290480105158
630284291.26981.374.292.759114829047097151

CURRENT RATING FOR SINGLE CORE 3.6/6KV(UM=7.2KV ) TO 18/30KV(UM=36KV) XLPE INSULATION

Nom. Cross-Section AreaBuried direct in GroundLaid in Single Way DuctLaid in Air
TrefoilFlat spacedTrefoilFlat TouchingTrefoilFlat TouchingFlat spaced
mm²AAAAAAA
70239246227229296303356
95285293271274361369434
120323332308311417426500
150361366343347473481559
185406410387391543550637
240469470447453641647745
300526524504510735739846
400590572564571845837938
5006506726046619359381118
630700882654771104510481318

Current Rating Conditions

Ground Temperature : 20°C

Ambient Temperature (air) : 30°C

Depth of Soil : 0.8m

Thermal Resistance of Soil : 1.5K•m/W