IEC 60332-1-2 vs IEC 60332-2-2: Fire Test Standards for Power and Control Cables

IEC 60332-1-2 vs IEC 60332-2-2: Fire Test Standards for Power and Control Cables

When it comes to selecting the right fire-resistant power and control cables, understanding flame test standards is essential. This article compares IEC 60332-1-2 and IEC 60332-2-2, both relevant to shielded instrument cables and small-diameter fire-resistant wiring in industrial applications.

1. Introduction to IEC 60332 Series

In modern electrical engineering, flame retardancy is a critical safety feature for cable design and installation. The IEC 60332 standard, established by the International Electrotechnical Commission (IEC), specifies test methods to assess the flame propagation characteristics of cables. The standard consists of multiple parts, including IEC 60332-1-2 and IEC 60332-2-2, each tailored to different cable types and applications.

1.1 IEC 60332-1-2 Overview

IEC 60332-1-2:2004 is titled "Tests on electric and optical fibre cables under fire conditions - Part 1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame." This standard outlines procedures to test the flame retardancy of single insulated wires or cables using a 1 kW pre-mixed flame. It simulates real-world fire conditions to evaluate the ability of the cable to limit flame spread when installed vertically.

1.2 IEC 60332-2-2 Overview

IEC 60332-2-2 applies to small-sized single insulated cables and uses a different flame source, specifically a diffused flame. It is suitable for cables with an overall diameter not exceeding 12 mm and is designed to replicate the performance of small-gauge wires under fire conditions.

2. Key Differences Between IEC 60332-1-2 and IEC 60332-2-2

While both standards are used to assess the flame retardancy of single insulated cables, they vary significantly in terms of flame intensity, applicable cable sizes, and testing methodology.

CriteriaIEC 60332-1-2IEC 60332-2-2
Flame Source1 kW pre-mixed flameDiffused flame
Sample Length600 mm600 mm
Applicable Cable DiameterAny sizeUp to 12 mm
Flame Angle45° incline45° incline
Flame Application Time60–480s (based on size)Fixed 20 seconds
Burner StandardIEC 60332-1-1IEC 60332-2-1
EvaluationSelf-extinguish; char length ≤540mmSame as 1-2

3. Application Guidance

IEC 60332-1-2 is generally used for standard-sized cables in industrial, commercial, and infrastructure applications. IEC 60332-2-2 is best suited for small electronic wiring, instrumentation cables, and confined environments where thin cables are used.

4. Conclusion

Choosing the correct flame retardancy standard depends on the cable size, application environment, and safety requirements. IEC 60332-1-2 offers a more rigorous test environment for larger cables, while IEC 60332-2-2 provides a focused method for smaller wires. Both standards aim to minimize fire hazards and ensure compliance with global safety practices.

Looking for compliant shielded instrumentation cables tested to IEC 60332 standards? Visit: Power and Control Cables