450/750V PVC Insulated, Non-sheathed Power Cables (Single Core 90°C)
APPLICATIONThis cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.STANDARDSBasic design to to BS EN 50525-2-31(formerly BS 6004:2000)FIRE PE…
450_750V PVC Insulated, Non-sheathed Power Cables (Single Core90℃ ).pdf Contact us

APPLICATION

This cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.

STANDARDS

Basic design to to BS EN 50525-2-31(formerly BS 6004:2000)

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)EN 60332-1-2

VOLTAGE RATING

450/750V

CABLE CONSTRUCTION

ConductorH05V-U: Class 1 solid copper conductor to BS EN 60228.

H05V-R: Class 2 stranded copper conductor to BS EN 60228.

H05V-K: Class 5 stranded copper conductor to BS EN 60228.
InsulationPVC Type TI 3 according to BS EN 50363-3

COLOUR CODE

Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation (PVC)90°C
Maximum short circuit temperature (5 Seconds)160°C
Minimum bending radiusUp to 8mm^2: 4 x overall diameter

8mm^2 to 12mm^2: 5 x overall diameter

Above 12mm^2: 6 x overall diameter

CONSTRUCTION PARAMETERS

ConductorFLP450-V2-U/R/K 
No. of Cores x Cross SectionClass of ConductorNominal Insulation ThicknessMaximum Overall DiameterApprox. Weight
No.xmm² mmmmkg/km
1x1.510.73.221
1x2.510.83.933
1x4.010.84.449
1x6.010.85.069
1x1011.06.4115
1x1.520.73.323
1x2.520.84.035
1x4.020.84.651
1x6.020.85.271
1x1021.06.7120
1x1621.07.8170
1x2521.29.7260
1x3521.210.9350
1x5021.412.8480
1x7021.414.6680
1x9521.617.1930
1x12021.618.81160
1x15021.820.91430
1x18522.023.31780
1x24022.226.62360
1x30022.429.62940
1x40022.633.23740
1x50022.836.94950
1x63022.841.16300
1x80022.845.78610
1x100023.051.010820
1x1.550.73.420
1x2.550.84.131
1x4.050.84.848
1x6.050.85.369
1x1051.06.8121
1x1651.08.1211
1x2551.210.2303
1x3551.211.7417
1x5051.413.9539
1x7051.416.0730
1x9551.618.2900
1x12051.620.21135
1x15051.822.51410
1x18552.024.91845
1x24052.228.42270

ELECTRICAL PROPERTIES

Conductor Operating Temperature90°C
Ambient Temperature30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E1A

Conductor cross- sectional areaReference Method A (enclosed in conduit in thermally insulating wall etc)Reference Method B (enclosed in conduit on a wall or in trunking etc)Reference Method C (clipped direct)Reference Method F (in free air or on a perforated cable tray, horizontal or vertical etc) TouchingReference Method G (in free air) Spaced by one cable diameter
2 cables, single- phase a.c. or d.c.3 or 4 cables, three -phase a.c.2 cables, single- phase a.c. or d.c3 or 4 cables, three- phase a.c.2 cables, single- phase a.c. or d.c. flat and touching3 or 4 cables, three- phase a.c. flat and touching or trefoil2 cables, single- phase a.c. or d.c. flat3 cables, three- phasea.c. flat3cables, three- phase a.c. trefoil2 cables, single- phase a.c. or d.c. or 3 cables three- phase a.c. flat
HorizontalVertical
123456789101112
mm²AAAAAAAAAAA
1.5191723202523-----
2.5262331283431-----
4.0353142374641-----
6.0454054485954-----
10615475668174-----
1681731008810999-----
2510695133117143130161141135182161
35131117164144176161200176169226201
50158141198175228209242216207275246
70200179253222293268310279268353318
95241216306269355326377342328430389
120278249354312413379437400383500454
150318285393342476436504464444577527
185362324449384545500575533510661605
240424380528450644590679634607781719
300486435603514743681783736703902833
400--68358486879394086882310851008
500--783666990904108399894612531169
630--900764113103312541151108814541362
800----1288117913581275121415811485
1000----1443132315201436134917751671

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E1B

Nominal Cross Section Area2 cables d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
Ref. Methods A and B (enclosed in conduit or trunking)Ref. Methods C, F & G(clipped direct, on trays or in free air)Ref. Methods A & B (enclosed in conduit or trunkingRef. Methods C, F & G (clipped direct, on trays or in free air)
Cables touchingCables spaced*Cables touching, TrefoilCables touching, FlatCables spaced*, Flat
123456789
mm²mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m
1.53131313127272727
2.51919191916161616
4.01212121210101010
6.07.97.97.97.96.86.86.86.8
104.74.74.74.74.04.04.04.0
162.92.92.92.92.52.52.52.5


rxzrxzrxzrxzrxzrxzrxz
251.851.850.311.901.850.1901.851.850.281.851.600.271.651.600.1651.601.600.1901.601.600.271.65
351.351.350.291.351.350.1801.351.350.271.351.150.251.151.150.1551.151.150.1801.151.150.261.20
500.991.000.291.050.990.1801.000.990.271.000.870.250.900.860.1550.870.860.1800.870.860.260.89
700.680.700.280.750.680.1750.710.680.260.730.600.240.650.590.1500.610.590.1750.620.590.250.65
950.490.510.270.580.490.1700.520.490.260.560.440.230.500.430.1450.450.430.1700.460.430.250.49
1200.390.410.260.480.390.1650.430.390.250.470.350.230.420.340.1400.370.340.1650.380.340.240.42
1500.320.330.260.430.320.1650.360.320.250.410.290.230.370.280.1400.310.280.1650.320.280.240.37
1850.250.270.260.370.260.1650.300.250.250.360.230.230.320.220.1400.260.220.1650.280.220.240.33
2400.1900.210.260.330.200.1600.250.1950.250.310.1850.220.290.1700.1400.220.1700.1650.240.1700.240.29
3000.1550.1750.250.310.1600.1600.220.1550.250.290.1500.220.270.1400.1400.1950.1350.1600.210.1350.240.27
4000.1200.1400.250.290.1300.1550.200.1250.240.270.1250.220.250.1100.1350.1750.1100.1600.1950.1100.240.26
5000.0930.1200.250.280.1050.1550.1850.0980.240.260.1000.220.240.0900.1350.1600.0880.1600.1800.0850.240.25
6300.0720.1000.250.270.0860.1550.1750.0780.240.250.0880.210.230.0740.1350.1500.0710.1600.1700.0680.230.24
8000.056---0.0720.1500.1700.0640.240.25---0.0620.1300.1450.0590.1550.1650.0550.230.24
10000.045---0.0630.1500.1650.0540.240.24---0.0550.1300.1400.0500.1550.1650.0470.230.24

Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance