450/750V PVC Insulated, Non-sheathed Power Cables (Single Core)
APPLICATIONThis cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. STANDARDSBasic design to BS EN 50525-2-31(formerly BS 6004:2000)FIRE PERF…
450_750V PVC Insulated, Non-sheathed Power Cables (Single Core).pdf Contact us

APPLICATION

This cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. 

STANDARDS

Basic design to BS EN 50525-2-31(formerly BS 6004:2000)

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)EN 60332-1-2

VOLTAGE RATING

450/750V

CABLE CONSTRUCTION

ConductorH05V-UClass 1 solid copper conductor to BS EN 60228.

H05V-RClass 2 stranded copper conductor to BS EN 60228.

H05V-KClass 5 stranded copper conductor to BS EN 60228.
InsulationPVC Type TI 1 according to BS EN 50363-3

COLOUR CODE

Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation (PVC)70°C
Maximum short circuit temperature (5 Seconds)160°C
Minimum bending radiusUp to 8mm²4 x overall diameter

8mm² to 12mm²5 x overall diameter

Above 12mm²6 x overall diameter

CONSTRUCTION PARAMETERS

ConductorFLP450-V-U/R/K 
No. of Cores x Cross SectionClass of ConductorNominal Insulation ThicknessMaximum Overall DiameterApprox. Weight
No.xmm² mmmmkg/km
1x1.510.73.221
1x2.510.83.933
1x4.010.84.449
1x6.010.85.069
1x1011.06.4115
1x1.520.73.323
1x2.520.84.035
1x4.020.84.651
1x6.020.85.271
1x1021.06.7120
1x1621.07.8170
1x2521.29.7260
1x3521.210.9350
1x5021.412.8480
1x7021.414.6680
1x9521.617.1930
1x12021.618.81160
1x15021.820.91430
1x18522.023.31780
1x24022.226.62360
1x30022.429.62940
1x40022.633.23740
1x50022.836.94950
1x63022.841.16300
1x80022.845.78610
1x100023.051.010820
1x1.550.73.420
1x2.550.84.131
1x4.050.84.848
1x6.050.85.369
1x1051.06.8121
1x1651.08.1211
1x2551.210.2303
1x3551.211.7417
1x5051.413.9539
1x7051.416.0730
1x9551.618.2900
1x12051.620.21135
1x15051.822.51410
1x18552.024.91845
1x24052.228.42270

ELECTRICAL PROPERTIES

Conductor Operating Temperature70°C
Ambient Temperature30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D1A

Conductor cross- sectional areaReference Method A (enclosed in conduit in thermally insulating wall etc)Reference Method B (enclosed in conduit on a wall or in trunking etc)Reference Method C (clipped direct)Reference Method F (in free air or on a perforated cable tray horizontal or vertical etc)
TouchingSpaced by one cable diameter
2 cables, single-phase a.c. or d.c.3 or 4 cables, three -phase a.c.2 cables, single-phase a.c. or d.c3 or 4 cables, three-phase a.c.2 cables, single-phase a.c. or d.c. flat and touching3 or 4 cables, three-phase a.c. flat and touching or trefoil2 cables, single-phase a.c. or d.c. flat3 cables, three-phase a.c. flat3 cables, three-phase a.c. trefoil2 cables, single-phase a.c. or d.c. or 3 cables three- phase a.c. flat
HorizontalVertical
123456789101112
mm²AAAAAAAAAAA
1.514.513.517.515.52018-----
2.5201824212725-----
4.0262432283733-----
6.0343141364743-----
10464257506559-----
16615676688779-----
25807310189114104131114110146130
359989125110141129162143137181162
50119108151134182167196174167219197
70151136192171234214251225216281254
95182164232207284261304275264341311
120210188269239330303352321308396362
150240216300262381349406372356456419
185273245341296436400463427409521480
240321286400346515472546507485615569
300367328458394594545629587561709659
400--546467694634754689656852795
500--626533792723868789749982920
630--720611904826100590585511381070
800----10309431086102097112651188
1000----1154105812161149107914201337

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D1B

Nominal Cross Section Area2 cables d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
Ref. Methods A and B (enclosed in conduit or trunking)Ref. Methods C & F(clipped direct, on trays or in free air)Ref. Methods A & B (enclosed in conduit or trunkingRef. Methods C & F (clipped direct, on trays or in free air)
Cables touchingCables spaced*Cables touching, TrefoilCables touching, FlatCables spaced*, Flat
123456789
mm²mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m
1.52929292925252525
2.51818181815151515
4.0111111119.59.59,59.5
6.07.37.37.37.36.46.46.46.4
104.44.44.44.43.83.83.83.8
162.82.82.82.82.42.42.42.4


rxzrxzrxzrxzrxzrxzrxz
251.751.800.331.801.750.201.751.750.291.801.500.291.551.500.1751.501.500.251.551.500.321.55
351.251.300.311.301.250.1951.251.250.281.301.100.271.101.100.1701.101.100.241.101.100.321.15
500.930.950.31.00.930.190.950.930.280.970.810.260.850.80.1650.820.80.240.840.80.320.86
700.630.650.290.720.630.1850.660.630.270.690.560.250.610.550.160.570.550.240.60.550.310.63
950.460.490.280.560.470.180.50.470.270.540.420.240.480.410.1550.430.410.230.470.40.310.51
1200.360.390.270.470.370.1750.410.370.260.450.330.230.410.320.150.360.320.230.40.320.30.44
1500.290.310.270.410.30.1750.340.290.260.390.270.230.360.260.150.30.260.230.340.260.30.4
1850.230.250.270.370.240.170.290.240.260.350.220.230.320.210.1450.260.210.220.310.210.30.36
2400.180.1950.260.330.1850.1650.250.1850.250.310.170.230.290.160.1450.220.160.220.270.160.290.34
3000.1450.160.260.310.150.1650.220.150.250.290.140.230.270.130.140.190.130.220.250.130.290.32
4000.1050.130.260.290.120.160.20.1150.250.270.120.220.250.1050.140.1750.1050.210.240.10.290.31
5000.0860.110.260.280.0980.1550.1850.0930.240.260.10.220.250.0860.1350.160.0860.210.230.0810.290.3
6300.0680.0940.250.270.0810.1550.1750.0760.240.250.080.220.240.0720.1350.150.0720.210.220.0660.280.29
8000.053---0.0680.150.1650.0610.240.25---0.060.130.1450.060.210.220.0530.280.29
10000.042---0.0590.150.160.050.240.24---0.0520.130.140.0520.20.210.0440.280.28

Note: *Spacings larger than one cable diameter will result in a large voltage drop.

r = conductor resistance at operating temperature

x = reactance

z = impedance