BFOU 0,6-1(1,2)kV, P5-P12 large single core cables
ApplicationsThese cables are fire resistant, flame retardant, low smoke, halogen free and mud resistant, used for control, power and lighting systems.StandardsIEC 60092-353IEC 60092-351IEC 60092-359IEC 60331-21IEC 60332-1IEC 60332-3-22IEC 60754-1,2IEC…
BFOU 0,6-1(1,2)kV, P5-P12 large single core cables.pdf Contact us

Applications

These cables are fire resistant, flame retardant, low smoke, halogen free and mud resistant, used for control, power and lighting systems.

Standards

  • IEC 60092-353

  • IEC 60092-351

  • IEC 60092-359

  • IEC 60331-21

  • IEC 60332-1

  • IEC 60332-3-22

  • IEC 60754-1,2

  • IEC 61034-1,2

  • NEK 606:2004

Construction

Electrical Characteristics

ConductorsTinned annealed stranded compacted copper to IEC 60228 class 2.
InsulationMica tape + Halogen free EPR/Mica tape + XLPE.
BeddingHalogen free compound.
ArmourTinned copper wire braid.
Outer SheathHalogen free thermosetting compound, SHF2 (for TYPE P5). Halogen free, mud resistant thermosetting compound, SHF MUD (for TYPE P5/P12), coloured black.

 

Nominal Cross Section Areamm^21.52.5461016253550
Nominal Conductor Diametermm1.62.12.63.245.16.57.48.7
Maximum DC Resistant@20℃Ω/km12.27.564.73.111.841.160.7340.5290.391
Continuous Current Rating@45℃1 CoreA233040527296127157196
Continuous Current Rating@45℃2 CoreA202634446182108133167
Continuous Current Rating@45℃3&4 CoreA16212836506789110137
Short Circuit Current 1sA21036057086014302290358050107150
Operating VoltageKV0.6/10.6/10.6/10.6/10.6/10.6/10.6/10.6/10.6/1

 

Nominal Cross Section Areamm^27095120150185240300400630
Nominal Conductor Diametermm10.312.213.815.117.019.621.924.632.5
Maximum DC Resistant@20℃Ω/km0.270.1950.1540.1260.10.07620.06070.04750.0286
Continuous Current Rating@45℃1 CoreA242293339389444522601690890
Continuous Current Rating@45℃2 CoreA206249288331444444511587757
Continuous Current Rating@45℃3&4 CoreA169205237272311365421483623
Short Circuit Current 1sA100201359017170214602647034340429305723090140
Operating VoltageKV0.6/10.6/10.6/10.6/10.6/10.6/10.6/10.6/10.6/1

Note: For more than 4-cores, the current ratings may be calculated from the following formula (IN I1 / N 3 = ), I1= Current rating for 1-core, N = Number of cores.

Ambient Temperature Correction Factors

Ambient Temperature Correction Factors35404550556065707580
Rating Factor1.11.051.00.940.880.820.740.670.580.47

Mechanical and Thermal Properties

Bending Radius8×OD (during installation)

6×OD (fixed installed)
Temperature Range-20℃ ~ +90℃