BFOU 0,6-1(1,2)kV, P5-P12 double braided
ApplicationsThese cables are fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100℃ hydrocarbon fire.StandardsIEC 60092-353 IEC 60092-351 IEC 6009…
BFOU 0,6-1(1,2)kV, P5-P12 double braided.pdf Contact us

Applications

These cables are fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100℃ hydrocarbon fire.

Standards

  • IEC 60092-353

  •  

  • IEC 60092-351

  •  

  • IEC 60092-359

  •  

  • IEC 60331-21

  •  

  • IEC 60332-1

  •  

  • IEC 60332-3-22

  •  

  • IEC 60754-1,2

  •  

  • IEC 61034-1,2

  •  

  • NEK 606:2004

Construction

Electrical Characteristics

ConductorsTinned annealed stranded compacted copper to IEC 60228 class 2.
InsulationMica tape + Halogen free EPR/XLPE.
BeddingHalogen free compound.
ArmourTinned copper wire braid.
Outer Sheath1Halogen free thermosetting compound, SHF2.
HC-fire protectionExtruded thermoplastic fire protection compound.
TapingLapped glass fibre tape.
Outer Sheath2Flame retardant halogen-free thermoplastic compound, SHF1,coloured black.

 

Nominal Cross Section Areamm^21.52.5461635
Nominal Conductor Diametermm1.62.12.63.25.17.4
Maximum DC Resistant@20℃Ω/km12.27.564.73.111.160.529
Continuous Current Rating@45℃1 CoreA2330405296157
Continuous Current Rating@45℃2 CoreA2026344482133
Continuous Current Rating@45℃3&4 CoreA1621283667110
Short Circuit Current 1sA21036057086022905010
Operating VoltageKV0.6/10.6/10.6/10.6/10.6/10.6/1
Nominal Cross Section Areamm^2507095120150185240300
Nominal Conductor Diametermm8.710.312.213.815.117.019.621.9
Maximum DC Resistant@20℃Ω/km0.3910.270.1950.1540.1260.10.07620.0607
Continuous Current Rating@45℃1 CoreA196242293339389444522601
Continuous Current Rating@45℃2 CoreA167206249288331444444511
Continuous Current Rating@45℃3&4 CoreA137169205237272311365421
Short Circuit Current 1sA715010020135901717021460264703434042930
Operating VoltageKV0.6/10.6/10.6/10.6/10.6/10.6/10.6/10.6/1

Note: For more than 4-cores, the current ratings may be calculated from the following formula (IN I1 / N 3 = ), I1= Current rating for 1-core, N = Number of cores.

Ambient Temperature Correction Factors

Ambient Temperature Correction Factors35404550556065707580
Rating Factor1.11.051.00.940.880.820.740.670.580.47

Mechanical and Thermal Properties

Bending Radius20×OD (during installation)

12×OD (fixed installed)
Temperature Range-20℃ ~ +90℃